Under the UPC, a long horizontal drainage run needs a cleanout every so many feet of developed length. What is the maximum spacing?
Not quite. The answer is C: 100 feet
The UPC wants a cleanout at the upper end of each horizontal drain and then one for every 100 feet of developed length (or fraction of it), plus an extra cleanout for each aggregate change of direction greater than 135 degrees. Washington's amendments restate the same 100-foot rule. Fifty feet is the figure candidates pick up from other codes, which is the usual wrong answer here.
Reference: WAC 2021 51-56-0700, §707.4 (Cleanout location and spacing)
Checked against the official text
More Washington Journeyman Plumber practice questions
Trade Code Wizard is not affiliated with, endorsed by, or licensed by the International Code Council (ICC), the National Fire Protection Association (NFPA), IAPMO, the ESCO Institute, NATE, HVAC Excellence, NASCLA, NICET, the U.S. Environmental Protection Agency, PSI, Prov, Pearson VUE, or any state or local licensing board. Exam and code names are used only to identify which examination this study material prepares you for.
These are original practice questions written to publicly published exam content outlines. They are not actual exam questions, and they do not reproduce code text. Explanations cite code sections and state requirements in our own words — always verify against the code edition your jurisdiction has adopted, which may differ from the edition cited here.