Per 430.22, motor branch-circuit conductors for a single continuous-duty motor must generally be sized at not less than what percentage of the motor's full-load current?
Not quite. The answer is C: 125%
430.22 sets the baseline at 125% of the motor's full-load current (taken from the Article 430 tables) for the branch-circuit conductors of a single continuous-duty motor. This is a motor-specific rule that happens to match the 125% used for continuous loads elsewhere.
Reference: NEC 2023 430.22 (Motor Branch-Circuit Conductor Sizing)
Checked against multiple published sources
Three sources agree on 125% of full-load current: an ECM quiz based on the 2023 NEC, an ECM guide, and a Mike Holt motor chart citing 430.22. None is the code text.
Trade Code Wizard is not affiliated with, endorsed by, or licensed by the International Code Council (ICC), the National Fire Protection Association (NFPA), IAPMO, the ESCO Institute, NATE, HVAC Excellence, NASCLA, NICET, the U.S. Environmental Protection Agency, PSI, Prov, Pearson VUE, or any state or local licensing board. Exam and code names are used only to identify which examination this study material prepares you for.
These are original practice questions written to publicly published exam content outlines. They are not actual exam questions, and they do not reproduce code text. Explanations cite code sections and state requirements in our own words — always verify against the code edition your jurisdiction has adopted, which may differ from the edition cited here.