Per Table 310.16, what is the allowable ampacity of a 6 AWG copper THWN conductor (75°C column), not more than three current-carrying conductors in a raceway?
Not quite. The answer is B: 65 A
6 AWG copper reads 55 A in the 60°C column, 65 A in the 75°C column, and 75 A in the 90°C column. THWN is a 75°C-rated insulation, so 65 A is the correct row/column intersection. Grabbing the 60°C or 90°C figure instead of matching the insulation's actual rating is the single most common lookup error on this table.
Reference: NEC 2023 Table 310.16 (Allowable Ampacity of Insulated Conductors)
Checked against multiple published sources
A Southwire spec sheet (ampacities stated as based on the 2023 NEC Table 310.16) and a Cerrowire ampacity chart agree on the 6 AWG copper values of 55/65/75 A. Neither is the code text.
Trade Code Wizard is not affiliated with, endorsed by, or licensed by the International Code Council (ICC), the National Fire Protection Association (NFPA), IAPMO, the ESCO Institute, NATE, HVAC Excellence, NASCLA, NICET, the U.S. Environmental Protection Agency, PSI, Prov, Pearson VUE, or any state or local licensing board. Exam and code names are used only to identify which examination this study material prepares you for.
These are original practice questions written to publicly published exam content outlines. They are not actual exam questions, and they do not reproduce code text. Explanations cite code sections and state requirements in our own words — always verify against the code edition your jurisdiction has adopted, which may differ from the edition cited here.